Fire Alarm Design and AutoCAD Services

A few of the other services I provide are Printing, Web Design, Graphic Design and Business Implementation.

What I do.

I provide all of the necessary documents required for a submittal to the authority having jurisdiction for a new fire alarm system. I start with the design of the system using AutoCad 2011, and provide 3 ea. color copies of the new design using a HP designjet. I then create the voltage drop calculations, the standby battery calculations and any other calculations needed, such as speaker draw, using excel spreadsheets. All of the specification sheets are included for all of the devices used in the installation. A cover sheet is also provided showing a material list and quantities. I can be listed under your company so that I may sign the drawings with my APS stamp. More information can be found on my website at FireAlarmDesigns.com

Wednesday, February 9, 2011

Synchronization

Synchronized Strobes


ADA recommends that a composite flash rate in excess of 5 Hz shall be avoided for multiple strobes installed in the field of view, and indicates that the use of synchronized strobes should provide an acceptable alternative when more than two strobes are installed in the same field of view. In addition, it is important to remember that in order to meet ADA’s concern for effectively alerting the hearing impaired, strobe flash rates must be a minimum of one flash per second, across the Regulated* voltage range. Using lower intensity synchronized strobes can provide better alerting since occupants can often directly view the strobe flash. In addition, the selection of strobe intensity and location is simplified.

Synchronized Temporal Pattern

NFPA 72 (Chapter 6, Sections 6.8.6.4) requires the use of the temporal pattern (Code 3) audible signal for public mode evacuation. To insure that the sounds from multiple signals within a specified area do not overlap and interfere with the distinctive temporal pattern, the devices shall be synchronized. Since a majority of fire alarm installations are retrofit applications, the ability to install synchronized appliances using two wires becomes a significant issue. With the use of two (2) wire signaling appliances, such as The Wheelock Series AS and NS, existing wiring may not have to be replaced unless the current capacity of the existing NAC circuit needs to be increased.

Evacuation Signal Zoning

NFPA 72 (Chapter 6, Section 6.8.6.4.3) requires synchronization of notification appliance circuits within an evacuation signaling zone.

No comments:

Post a Comment