I provide all of the necessary documents required for a submittal to the authority having jurisdiction for a new fire alarm system. I start with the design of the system using AutoCad 2011, and provide 3 ea. color copies of the new design using a HP designjet. I then create the voltage drop calculations, the standby battery calculations and any other calculations needed, such as speaker draw, using excel spreadsheets. All of the specification sheets are included for all of the devices used in the installation. A cover sheet is also provided showing a material list and quantities. I can be listed under your company so that I may sign the drawings with my APS stamp. More information can be found on my website at FireAlarmDesigns.com

Wednesday, February 9, 2011

Sleeping Rooms

A visual appliance used to awaken a sleeping, hearing impaired person shall be permanently installed and located 16 feet maximum from the pillow or “head of the bed” location, measured horizontally. Wall mounted appliances located at least 24 inches below the ceiling shall have a minimum effective intensity of 110 candela. Ceiling mounted appliances and wall mounted appliances located less than 24 inches below the ceiling are to have a minimum effective intensity of 177 candela. If a suite contains more than one sleeping area, an appliance shall be provided in each sleeping area.