Hello xxxxx,
Below is typical language used in plan review letters regarding vo
drop calculations. This is the current policy enforced by the Dal
Fire-Rescue Department for all fire alarm plan reviews.
"All circuit voltage drops shall be limited to no more than 15%, o
volts for a 24 volt system. Circuit #1 serving the 2nd and 3rd fl
of Building Type I exceeds the maximum allowable voltage drop (see
attached calculation sheet). The contractor shall provide circuit
that the maximum voltage drop does not exceed 3.6 volts. Provide
battery capacity and voltage drop calculations that reflect change
the alarm notification system."
As mentioned, a copy of the Dallas amendments to Chapter 9 of the
International Fire Code are available from myself or any of the ot
engineers at 320 E. Jefferson St., Room 105. A complete set of th
Building and Fire Code amendments can be purchased at the cashier'
in Room 118.