Audible Notification
Audible notification appliances intended for operation in the public mode shall have a sound level of not less than 15 dBA above the average ambient sound level or 5 dBA above the maximum sound level having a duration of at least 60 seconds, whichever is greater, measured 5 ft. above the floor.